The gold standard. The most effective ventilation systems include a heat-recovery ventilator (HRV(HRV). Balanced ventilation system in which most of the heat from outgoing exhaust air is transferred to incoming fresh air via an air-to-air heat exchanger; a similar device, an energy-recovery ventilator, also transfers water vapor. HRVs recover 50% to 80% of the heat in exhausted air. In hot climates, the function is reversed so that the cooler inside air reduces the temperature of the incoming hot air. ) or energy-recovery ventilator (ERV(ERV). The part of a balanced ventilation system that captures water vapor and heat from one airstream to condition another. In cold climates, water vapor captured from the outgoing airstream by ERVs can humidify incoming air. In hot-humid climates, ERVs can help maintain (but not reduce) the interior relative humidity as outside air is conditioned by the ERV.) — similar appliances that transfer heat (but not air) between a ventilation system's exhaust and supply air streams.
UPDATED 12/20/2012
Most green builders include some type of mechanical ventilation system in every home they build. That’s good. Since green buildings usually have very low levels of air leakage, mechanical ventilation is usually essential.
Unfortunately, several research studies have shown that a high number of mechanical ventilation systems are poorly designed or installed. Among the common problems:
It’s disheartening to learn that many green homes waste energy because of poorly designed ventilation systems that were improperly commissioned.
If you’re unfamiliar with residential ventilation systems, it’s a good idea to review the ventilation information in the GreenBuildingAdvisor encyclopedia.
ASHRAE’s residential ventilation standard (Standard 62.2) sets the minimum ventilation rate at 7.5 cfm per occupant plus 3 cfm for every 100 square feet of occupiable floor area.
GBA Encyclopedia: Ventilation Choices
Ventilation Rates and Human Health
Joseph Lstiburek: Just Right and Airtight
Systems complying with ASHRAE 62.2A standard for residential mechanical ventilation systems established by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers. Among other requirements, the standard requires a home to have a mechanical ventilation system capable of ventilating at a rate of 1 cfm for every 100 square feet of occupiable space plus 7.5 cfm per occupant. have ventilation rates that are relatively low; for example, a 2,000-square-foot house with three occupants requires 83 cfm of mechanical ventilation. That’s about as much airflow as is provided by a typical bath exhaust fan.
Since ventilation airflows are typically quite low, ventilation ductwork needs to be impeccably sealed. If ventilation ductwork is leaky, fresh air won’t reach its intended destination.
Prominent building scientists are now debating the merits of the ASHRAE 62.2 ventilation rate. Max Sherman, former chairman of the ASHRAE 62.2 committee, defends the existing ASHRAE formula. On the other hand, Joseph Lstiburek, the well-known building scientist and gadfly, argues that the existing ASHRAE ventilation rate is too high, resulting in unnecessarily high energy costs — especially in hot humid climates, where the introduction of high volumes of outdoor air increases the need for cooling and dehumidification.
Lstiburek and Armin Rudd, a fellow engineer at the Building Science Corporation, advise designers of Building America houses to ventilate at a lower rate. “These [Building America] homes have roughly 50 to 60 percent of the ventilation rate required by ASHRAE standard 62.2,” Rudd has written. “The lack of complaints by occupants indicates that the systems are working to provide indoor air quality acceptable to the occupants.”
The “great rate debate” is far from settled; stay tuned. (For more information on this topic, see Ventilation Rates and Human Health.)
As more and more local building codes include ventilation requirements, fewer builders are able to get away with building new homes without mechanical ventilation. However, a few die-hard holdouts defend homes without mechanical ventilation.
One reason why homes without mechanical ventilation systems work better than expected is that many common household appliances act just like exhaust-only ventilationMechanical ventilation system in which one or more fans are used to exhaust air from a house and make-up air is supplied passively. Exhaust-only ventilation creates slight depressurization of the home; its impact on vented gas appliances should be considered. systems. Such appliances include:
When these appliances are operating, fresh outdoor air enters a house through random cracks to replace the air that is exhausted.
However, homes without ventilation systems are homes of the past. The building science community has reached a consensus: build tight and ventilate right.
After two decades of experimentation, builders have narrowed ventilation options down to four main options:
Some builders worry that a supply-only ventilation system (for example, central-fan-integrated supply ventilation) won’t work in a cold climate, because the ventilation fan will drive interior air into building cavities where moisture can condense.
This worry is needless. As energy expert Bruce Harley explains, “The upper portions (walls and ceilings) of every home — typically most of the second floor in two-story homes — already operate under positive air pressure in cold weather, due to the stack effectAlso referred to as the chimney effect, this is one of three primary forces that drives air leakage in buildings. When warm air is in a column (such as a building), its buoyancy pulls colder air in low in buildings as the buoyant air exerts pressure to escape out the top. The pressure of stack effect is proportional to the height of the column of air and the temperature difference between the air in the column and ambient air. Stack effect is much stronger in cold climates during the heating season than in hot climates during the cooling season.. The relatively small airflow of most supply-only ventilation systems (75 cfm to 150 cfm) will have little effect on this situation other than to shift the neutral pressure plane down slightly, in all but the very tightest of homes. … In cold climates, I believe that distributed, supply-only ventilation such as that supplied by a ducted distribution system controlled by an AirCycler, or other ducted low-flow supply ventilation, is vastly preferable to single or multi-port exhaust-only systems, except in extremely tight homes (in which case balanced supply and exhaust ventilation is the best choice).”
As Harley’s comments make clear, many energy experts (including Lstiburek) disparage exhaust-only ventilation systems. The main argument against exhaust-only ventilation systems — for example, a Panasonic bath exhaust fan controlled by a timer — is that they don’t provide adequate distribution of fresh air. As a result, some rooms have plenty of fresh air while other rooms remain stuffy.
According to some ventilation experts, ASHRAE 62.2 — which currently lacks any provision requiring fresh-air distribution — should be revised to include a distribution requirement. Armin Rudd has written, “I think distribution of ventilation air is an important issue. Bringing in ventilation air and hoping that it will provide adequate indoor air quality throughout the whole house is just a hope and a prayer.”
Research shows, however, that in some homes — especially small homes with an open floor plan — exhaust-only ventilation systems work well. If the exhaust fan is well chosen — my own favorite is the Panasonic Whisper Green fan, which uses only 11.3 watts to move 80 cfm — exhaust-only ventilation systems have very low installation and operating costs.
If you choose this type of ventilation system, it’s important to remember to undercut the bathroom door.
If you do install an exhaust-only ventilation system, don’t bother installing passive fresh air inlets in the walls. Fresh air will find its way into the home through random cracks.
A 2000 Vermont study (“A Field Study of Exhaust-Only Ventilation System Performance in Residential New Construction In Vermont”) by Andy Shapiro, David Cawley, and Jeremy King, investigated whether passive fresh air inlets make any sense. The researchers studied 43 new homes (22 of which had passive fresh air vents) with exhaust-only ventilation systems. They wrote, “When the EOV [exhaust-only ventilation] fan was operating, 35% of the vents were exhausting inside air, 48% were supplying outside air, and 17% of the vents were not moving air.” The explanation? “The pressures induced by fans in these [studied homes] … were low relative to pressures induced on a house by natural forces, including wind and temperature-driven stack effectAlso referred to as the chimney effect, this is one of three primary forces that drives air leakage in buildings. When warm air is in a column (such as a building), its buoyancy pulls colder air in low in buildings as the buoyant air exerts pressure to escape out the top. The pressure of stack effect is proportional to the height of the column of air and the temperature difference between the air in the column and ambient air. Stack effect is much stronger in cold climates during the heating season than in hot climates during the cooling season..”
For years, the engineers at the Building Science Corporation have been singing the praises of central-fan-integrated supply ventilation systems. These systems can only be used in homes with forced-air heating or cooling systems. The systems include three important components:
The AirCycler control (also known as a FanCycler) prevents both underventilation and overventilation. When the AirCycler notices that the furnace fan hasn’t operated for a long time, the control turns on the fan to prevent underventilation. When the control notices that the fan has been operating continuously for a long time, the control closes the motorized damper to prevent overventilation.
During the swing seasons — spring and fall — the furnace blower will need to operate for ventilation purposes. In most climates, about 15% of the annual blower run time for such systems will be devoted to ventilation only. If the system is properly commissioned, the furnace will supply a 7% outside air fraction during ventilation mode.
The big downside to central-fan-integrated supply ventilation is that the installer needs to understand how to design and commission the system. HVAC(Heating, ventilation, and air conditioning). Collectively, the mechanical systems that heat, ventilate, and cool a building. contractors capable of this task are rare. Unless the designer of a central-fan-integrated ventilation system takes great care when specifying the furnace and programming blower operation, such a system can have unreasonably high operating costs.
A well-designed central-fan-integrated supply ventilation system needs a furnace with an energy-efficient ECM blower. Such furnaces cost between $1,000 and $1,500 more than conventional furnaces. If you end up using a furnace with a conventional blower motor — that is, one that draws 700 to 800 watts — the ventilation system will incur a big energy penalty. (For purposes of comparison, a Panasonic exhaust fan draws 11.3 watts, and most HRVs draw 100 watts or less).
Duct systems and fans designed for heating and cooling are not optimized for ventilation. While ventilation airflow is typically in the range of 50 to 100 cfm, furnace fans move as much as 1,200 to 1,400 cfm. One study (Robb Aldrich, Chicago, 2005) found that a poorly designed central-fan-integrated supply ventilation system in a house with an 800-watt furnace fan used 347 kWh of electricity for ventilation during a swing-season month. During the same month, an identical home with an exhaust-only ventilation system used only 6% as much electricity for ventilation. Although the researchers were somewhat worried that the exhaust-only ventilation system might be ineffective, the data were reassuring: all of the rooms had very acceptable CO2 readings.
Some builders worry that central-fan-integrated supply ventilation systems won’t work in a cold climate, where cold outdoor air might damage the furnace. According to Armin Rudd, such concerns are baseless — as long as the ventilation system is well designed.
Assuming a high outdoor air fraction (15%) and a low outdoor temperature (-30°F), the furnace will experience mixed return-air temperatures no colder than 55°F, as long as the thermostat is set to 70°F. Even in Chicago, such systems work well.
To reduce costs, some builders install the lazy man’s version of a central-fan-integrated supply ventilation system — one that includes a passive fresh air duct to the return-air plenum, but without a motorized damper or AirCycler control.
What’s wrong with this approach?
The best ventilation performance and lowest operating cost comes from an HRV or ERV with dedicated ventilation ductwork. Such a “gold standard” system should be designed to pull stale air from bathrooms and laundry rooms, while introducing fresh air to the living room and bedrooms.
Although HRVs and ERVs save energy compared to exhaust-only or supply-only ventilation systems, they are expensive to install. The high cost of these systems raises questions about their cost-effectiveness, especially in mild climates. To learn more about this issue, see Are HRVs Cost-Effective?
For ventilation purposes, either an HRV or an ERV can work well in any climate. The presumed advantage of ERVs over HRVs in hot, humid climates is not based on research or field data. As Max Sherman has written, “Almost all hot, humid climates have hours when it is dryer outside than inside, and then ERVs actually make the [indoor] moisture problem worse. The net effect this that ERVs are about a wash [compared to HRVs] for humidity control in those climates.” (For more information on this topic, see "HRV or ERV?")
The Lunos fan is a new type of ventilation fan from Germany. Installed in pairs, the wall-mounted ventilation fans automatically alternate between exhaust mode and supply mode. Because each fan includes a ceramic core, they are able to recover heat from the exhaust air stream.
These fans are particularly useful for retrofit applications, or for any situation where the installation of ductwork would be awkward. For more information, see European Products for Building Tight Homes.
Anyone who commissions a ventilation system needs to learn how to measure airflow. Manufacturers offer an array of accurate (and expensive) instruments to measure airflow. However, builders who need to troubleshoot problems may be interested in several low-cost methods of measuring airflow:
Last week’s blog: “Farewell to the Chimney?”